Skip to main content
Speclore

Steam Radiator Convector

Reference data and engineering information about steam radiator convector for hvac systems applications.

steamradiatorconvector

Overview

Engineering reference data for Steam Radiator Convector in HVAC systems.

Key Formulas

Sensible Heat

Q=m˙cpΔTQ = \dot{m} c_p \Delta T

Heat causing temperature change.

Latent Heat

Q=m˙hfgΔωQ = \dot{m} h_{fg} \Delta\omega

Heat causing moisture change.

COP (Cooling)

COP=Qc/WCOP = Q_c / W

Coefficient of performance.

Variables

Symbol Description Unit
QQ Heat transfer W
m˙\dot{m} Mass flow rate kg/s
cpc_p Specific heat of air J/(kg·K)
ΔT\Delta T Temperature difference K

Temperature Correction Coefficients

The heat capacity formulas assume standard temperature conditions. For actual operating conditions, temperature correction coefficients must be applied:

Radiator Correction Coefficient (λ_r): λr=(215F70Ftstr)1.3\lambda_r = \left( \frac{215^\circ\text{F} - 70^\circ\text{F}}{t_s - t_r} \right)^{1.3}

  • tst_s = average steam temperature (°F)
  • trt_r = room temperature (°F)

Convector Correction Coefficient (λ_c): λc=(215F65Ftsti)1.5\lambda_c = \left( \frac{215^\circ\text{F} - 65^\circ\text{F}}{t_s - t_i} \right)^{1.5}

  • tst_s = steam temperature (°F)
  • tit_i = inlet air temperature (°F)

Both coefficients equal 1 at their reference conditions (70°F room temp for radiators, 65°F inlet for convectors with 215°F steam).