Air Change Rate

Reference data and engineering information about air change rate for hvac systems applications.

airchangerate

Overview

Engineering reference data for Air Change Rate in HVAC systems.

Key Formulas

Sensible Heat

Q=m˙cpΔTQ = \dot{m} c_p \Delta T

Heat causing temperature change.

Latent Heat

Q=m˙hfgΔωQ = \dot{m} h_{fg} \Delta\omega

Heat causing moisture change.

COP (Cooling)

COP=Qc/WCOP = Q_c / W

Coefficient of performance.

Variables

Symbol Description Unit
QQ Heat transfer W
m˙\dot{m} Mass flow rate kg/s
cpc_p Specific heat of air J/(kg·K)
ΔT\Delta T Temperature difference K

Typical Air Change Rates

For well-insulated spaces, recommended air changes per hour depend on the building's exposure to outdoor air:

Worked Example

Problem: Calculate the air change rate for a room with an air flow of 3 m³/s and a volume of 20,000 m³.

Solution: Using the SI unit formula:

n=3600×qV=3600×3 m3/s20000 m3=0.54 h1n = \frac{3600 \times q}{V} = \frac{3600 \times 3 \text{ m}^3\text{/s}}{20000 \text{ m}^3} = 0.54 \text{ h}^{-1}

This means the room's air is replaced approximately once every 1.85 hours (1/0.541.851/0.54 \approx 1.85).