Reference data and engineering information about natural draught ventilation for hvac systems applications.

naturaldraughtventilation

Overview

Engineering reference data for Natural Draught Ventilation in HVAC systems.

Key Formulas

Sensible Heat

Q=m˙cpΔTQ = \dot{m} c_p \Delta T

Heat causing temperature change.

Latent Heat

Q=m˙hfgΔωQ = \dot{m} h_{fg} \Delta\omega

Heat causing moisture change.

COP (Cooling)

COP=Qc/WCOP = Q_c / W

Coefficient of performance.

Variables

Symbol Description Unit
QQ Heat transfer W
m˙\dot{m} Mass flow rate kg/s
cpc_p Specific heat of air J/(kg·K)
ΔT\Delta T Temperature difference K

Worked Example: Two-Story House

This example demonstrates calculating air flow due to natural draft in a two-story house.

Given:

  • Height between outlet and inlet air (h): 8 m
  • Outside temperature (t_o): -10 °C
  • Inside temperature (t_i): 20 °C
  • Duct hydraulic diameter (d_h): 0.2 m
  • Duct length (l): 3.5 m
  • Minor loss coefficient sum (Σξ): *1
  • Friction coefficient (λ): *0.019 (for galvanized steel)

1. Calculate Air Densities: Using the density-temperature relation ρ=353273+t\rho = \frac{353}{273 + t}: ρo=353273+(10)=1.342kg/m3\rho_o = \frac{353}{273 + (-10)} = 1.342 \, \text{kg/m}^3 ρi=353273+20=1.205kg/m3\rho_i = \frac{353}{273 + 20} = 1.205 \, \text{kg/m}^3

2. Calculate Duct Air Velocity: v=2g(ρoρi)hλlρidh+Σξρi=29.81(1.3421.205)80.0193.51.2050.2+11.2053.7m/sv = \sqrt{\frac{2 g (\rho_o - \rho_i) h}{\frac{\lambda l \rho_i}{d_h} + \Sigma\xi \rho_i}} = \sqrt{\frac{2 \cdot 9.81 \cdot (1.342 - 1.205) \cdot 8}{\frac{0.019 \cdot 3.5 \cdot 1.205}{0.2} + 1 \cdot 1.205}} \approx 3.7 \, \text{m/s}

3. Calculate Air Flow Volume: q=πdh24v=π(0.2)243.70.12m3/sq = \frac{\pi d_h^2}{4} \cdot v = \frac{\pi \cdot (0.2)^2}{4} \cdot 3.7 \approx 0.12 \, \text{m}^3/\text{s}

Note: These equations apply to dry air. For mass flow and energy loss calculations, the effects of air humidity can be significant and must be considered separately.

Major and Minor System Loss

The natural draft force is balanced against the pressure losses in the duct system. The total pressure loss (dp) due to friction (major loss) and fittings (minor loss) is given by:

dp=λ(ldh)ρiv22+Σξ12ρiv2dp = \lambda \left(\frac{l}{d_h}\right) \frac{\rho_i v^2}{2} + \Sigma\xi \frac{1}{2} \rho_i v^2

where:

  • λ\lambda = Darcy-Weisbach friction coefficient
  • ll = length of duct or pipe (m)
  • dhd_h = hydraulic diameter (m)
  • Σξ\Sigma\xi = sum of minor loss coefficients

References