Recommended 通風 rates 與 空氣 changes per hour 用于 various building spaces 與 applications.

ventilationrates

Overview

Ventilation is the process of supplying fresh outdoor air to an enclosed space and removing stale indoor air. Adequate ventilation is essential for:

  • Indoor air quality (IAQ)
  • Occupant health and comfort
  • Moisture and odor control
  • Dilution of indoor pollutants

Air Changes Per Hour (ACH)

The number of times the entire air volume in a room is replaced per hour:

ACH=QVACH = \frac{Q}{V}

where:

  • QQ = ventilation air flow rate (m³/h)
  • VV = room volume (m³)

ASHRAE 62.1 Ventilation Rates

ASHRAE Standard 62.1 specifies minimum ventilation rates based on per person and per floor area:

Vbz=RpPz+RaAzV_{\text{bz}} = R_p \cdot P_z + R_a \cdot A_z

where:

  • RpR_p = outdoor air per person (L/s per person)
  • PzP_z = zone population
  • RaR_a = outdoor air per floor area (L/s per m²)
  • AzA_z = zone floor area (m²)
Occupancy Category RpR_p (L/s per person) RaR_a (L/s per m²)
Office space 2.5 0.3
Conference/meeting 2.5 0.3
Classroom (5+) 5.0 0.6
Retail sales 3.8 0.6

Key Points

  • Ventilation rates are typically higher for spaces with more occupants or more pollutant sources
  • Hospitals and laboratories require the highest ventilation rates for contamination control
  • Energy-efficient ventilation uses heat recovery (HRV/ERV) to reclaim energy from exhaust air
  • CO₂ monitoring can be used for demand-controlled ventilation (DCV)