Skip to main content
Speclore

莫里爾圖(i-x 圖)/焓濕圖:濕空氣範例

讀取濕空氣莫里爾 i-x 圖或焓濕圖中的焓、含濕量和濕球溫度,並查看 HVAC 計算範例。

psychrometricchartmollier計算器數據表

概述

The Mollier diagram (also called the Mollier i-x chart) is a graphical representation of the thermodynamic properties of moist air. It plots enthalpy against specific humidity (moisture content), with overlay lines for dry bulb temperature, wet bulb temperature, and relative humidity. The Mollier diagram is a rotated variant of the standard psychrometric chart and is widely used in HVAC system design for analyzing heating, cooling, humidification, dehumidification, and air mixing processes.

關键公式

Humidity Ratio (Specific Humidity)

ω=0.622PvPa\omega = 0.622 \frac{P_v}{P_a}

The mass of water vapor per unit mass of dry air, where PvP_v is the partial pressure of water vapor and PaP_a is the partial pressure of dry air.

Relative Humidity

ϕ=PvPvs×100%\phi = \frac{P_v}{P_{vs}} \times 100\%

The ratio of actual vapor pressure to saturation vapor pressure at the same dry bulb temperature.

Enthalpy of Moist Air

h=cpTdb+ωhgh = c_p \cdot T_{db} + \omega \cdot h_g

Sensible heat plus latent heat per unit mass of dry air. The constant cp1.006c_p \approx 1.006 kJ/(kg·°C) for dry air and hgh_g is the enthalpy of saturated water vapor at the given temperature.

Wet Bulb Temperature

TwbTdbPvsPvγT_{wb} \approx T_{db} - \frac{P_{vs} - P_v}{\gamma}

此近似式將濕球溫差與水蒸氣壓差聯繫起來,其中 γ\gamma 為乾濕球常數(在 1 atm 下約為 66.6 Pa/°C)。

變量

9
單位
ω (omega)Humidity ratio (specific humidity)kg/kg dry air
φ (phi)相對濕度%
PvPartial pressure of water vaporPa
PvsSaturation vapor pressure at TdbPa
Tdb干球 temperature°C
TwbWet bulb temperature°C
hSpecific enthalpy of moist airkJ/kg dry air
cpSpecific heat of dry air at constant pressurekJ/(kg·°C)
hgEnthalpy of saturated water vaporkJ/kg

來源: engineeringtoolbox.com

Example: Reading the Mollier Diagram

Case 1 — Known: Dry Bulb Temperature and Relative Humidity

Given Tdb = 21 °C and φ = 50%, read the following from the Mollier chart:

3
數值
Enthalpy (h)~40 kJ/kg dry air
Wet Bulb Temp (Twb)~14.5 °C
~0.0076 kg/kg dry air

來源: engineeringtoolbox.com

Case 2 — Known: Dry Bulb and Wet Bulb Temperatures

Given Tdb = 19 °C and Twb = 12 °C, read:

2
數值
Enthalpy (h)~33 kJ/kg dry air
~0.0056 kg/kg dry air

來源: engineeringtoolbox.com

Saturation Vapor Pressure Reference

The saturation vapor pressure PvsP_{vs} increases sharply with temperature. Representative values from the Antoine equation or steam tables:

9
飽和 vapor pressure and latent heat of vaporization for water at standard atmospheric pressure
溫度 (°C)
飽和 蒸氣 壓力 (Pa)
焓 of 飽和 蒸氣 (kJ/kg)
06112501
58722510
1012282520
1517052529
2023392538
2531692547
3042462556
3556282565
4073842574

來源: engineeringtoolbox.com

飽和 蒸氣 壓力 vs. Dry Bulb 溫度

Mollier Chart Example Points

The original images show example readings from the Mollier chart. The extracted readings are represented below as data so they can be inspected without relying only on the bitmap chart.

2
圖表 case
干球 (°C)
相對濕度 (%)
濕球 (°C)
含濕量 (kg/kg dry air)
(kJ/kg dry air)
Dry bulb 21 °C and 50% RH215014.50.007640
Dry bulb 19 °C and wet bulb 12 °C1940120.005633

來源: engineeringtoolbox.com

Extracted Mollier 示例 States

Mollier Diagram Reproduction

The original Mollier diagram is redrawn below as an equation-generated psychrometric chart for moist air at standard atmospheric pressure. The chart uses humidity ratio on the horizontal axis and dry-bulb temperature on the vertical axis, with relative-humidity curves, constant-enthalpy lines, humidity-ratio grid lines, and the saturation boundary.

-25-20-15-10-505101520253035400.0000.0050.0100.015tdegCxkg/kg-20-100102030400.30.40.50.60.70.80.910-1510
Redrawn psychrometric Mollier reference chart for moist air at 101.325 kPa. Curves are generated from standard equations for saturation vapor pressure, humidity ratio, dry-bulb temperature, and moist-air enthalpy.
3
計算d from equations
原始 chart reading
21 °C dry bulb, 50% RHω = 7.71 g/kg, h = 40.71 kJ/kgω ≈ 7.6 g/kg, h ≈ 40 kJ/kg
19 °C dry bulb, ω = 5.6 g/kgh = 33.32 kJ/kg, RH ≈ 41%h ≈ 33 kJ/kg, RH ≈ 40%
0 °C saturationω = 3.77 g/kg, h = 9.44 kJ/kgsaturation boundary near 0 °C

來源: engineeringtoolbox.com

Mollier vs. Psychrometric Chart

The Mollier diagram and the standard ASHRAE psychrometric chart display the same thermodynamic data but with different axis orientations:

6
Mollier (i-x) 圖表
焓濕 圖表
Horizontal axisHumidity ratio (ω)干球 temperature
Vertical axisEnthalpy (h)Humidity ratio (ω)
Temperature linesNearly horizontal, slight slopeVertical
Enthalpy linesNearly verticalDiagonal
RH curvesUpward concaveUpward concave
Common regionEurope, industrial HVACNorth America, ASHRAE standard

來源: engineeringtoolbox.com

Calculator: Humidity Ratio from Vapor Pressure

Moist 空氣 State from 溫度 and Relative Humidity

單位換算器

焓濕 單位 转換器

Note: the direct kJ/kg to Btu/lb conversion preserves the metric enthalpy reference. The IP psychrometric enthalpy value uses the common inch-pound psychrometric reference and should be used when comparing with IP psychrometric charts.

Mollier Chart Reading Examples

The annotated example charts below are redrawn from the same psychrometric equations used by the main chart.

-25-20-15-10-505101520253035400.0000.0050.0100.015tdegCxkg/kg-20-100102030400.30.40.50.60.70.80.91State of air0-1510
Example reading: 21 degC dry-bulb temperature and 50% relative humidity gives about 7.7 g/kg humidity ratio and 40.7 kJ/kg enthalpy.
-25-20-15-10-505101520253035400.0000.0050.0100.015tdegCxkg/kg-20-100102030400.30.40.50.60.70.80.91State of air0-1510
Example reading: 19 degC dry-bulb temperature and 12 degC wet-bulb temperature gives about 5.6 g/kg humidity ratio and 33 kJ/kg enthalpy.

工程要點

  • Atmospheric pressure matters. The Mollier diagram is typically drawn for standard atmospheric pressure (101.325 kPa). At significantly different altitudes or pressures, corrections are needed or a pressure-specific chart should be used.
  • Axis orientation can confuse users. In the Mollier chart enthalpy runs nearly vertically and humidity ratio nearly horizontally, which is the reverse of what many ASHRAE-trained engineers expect. Verify which axis convention your chart uses before reading values.
  • Chart accuracy. Reading values from a printed chart introduces interpolation error. For precise calculations use the governing equations or digital psychrometric tools rather than visual interpolation.
  • Wet bulb temperature approximations. The formula TwbTdbPvsPvγT_{wb} \approx T_{db} - \frac{P_{vs} - P_v}{\gamma} is a linearization. For high accuracy, use iterative thermodynamic models (e.g., ASHRAE's formulation) or ASHRAE Psychrometric Chart No. 1.
  • Process visualization. The Mollier diagram excels at visualizing air-handling processes: sensible heating moves horizontally to the right; cooling and dehumidification move down and left; mixing of two airstreams follows a straight line between their state points.
  • Saturation line. The curved boundary on the Mollier chart represents 100% relative humidity. Air states cannot exist above (to the right of) this line—condensation occurs beyond saturation.

參考资料