風管計算器:摩擦損失、流速與壓降
根據風量、直徑、長度、粗糙度、密度和黏度,計算直管段內的空氣流速、雷諾數、達西摩擦因子和壓降。
概述
Use this calculator for the straight-duct portion of an HVAC pressure-drop estimate. Enter airflow, diameter (or an equivalent hydraulic diameter), length, wall roughness, air density, and dynamic viscosity to calculate velocity, Reynolds number, Darcy friction factor, and total friction loss. Fittings, dampers, transitions, and grilles require additional local-loss terms.
The source page is preserved at Engineering ToolBox — Air Duct Calculator; the original external calculator reference was http://www.iklimnet.com/data/duct.html.
關键公式
Darcy-Weisbach Equation
Pressure drop due to friction along a straight duct section.
Swamee-Jain Approximation (Friction Factor)
Valid for turbulent flow () in commercial ductwork.
Reynolds Number
Determines flow regime: laminar (), transitional, or turbulent (). Nearly all HVAC duct systems operate in the turbulent range.
Hydraulic Diameter
For non-circular ducts, where is cross-sectional area and is the wetted perimeter. For a round duct, equals the duct diameter.
Velocity Pressure
Useful for relating velocity to pressure and for sizing fittings.
變量
| 符號 | 說明 | Typical Unit |
|---|---|---|
| Friction pressure drop | Pa | |
| Darcy friction factor | — | |
| Duct length | m | |
| Hydraulic diameter | m | |
| Air density | kg/m³ | |
| Mean air velocity | m/s | |
| Reynolds number | — | |
| Absolute surface roughness | m | |
| Dynamic viscosity | Pa·s | |
| Cross-sectional area | m² | |
| Wetted perimeter | m |
Duct Material Roughness
风管 材料 | (mm) | (ft) |
|---|---|---|
| Galvanized steel | 0.046 | 0.00015 |
| Commercial steel | 0.045 | 0.00015 |
| Drawn tubing (copper) | 0.0015 | 0.000005 |
| Cast iron | 0.26 | 0.00085 |
| Concrete | 0.3 | 0.001 |
| Flexible duct (smooth liner) | 0.09 | 0.0003 |
| Flexible duct (corrugated) | 0.9 | 0.003 |
| Fiberglass duct board | 0.3 | 0.001 |
| PVC pipe | 0.0015 | 0.000005 |
| Sheet metal (uncoated) | 0.05 | 0.00016 |
來源: engineeringtoolbox.com
Standard Air Properties
溫度 (°C) | 密度 (kg/m³) | Dynamic 黏度 (Pa·s (×10⁻⁵)) |
|---|---|---|
| 0 | 1.293 | 1.715 |
| 10 | 1.247 | 1.765 |
| 20 | 1.204 | 1.815 |
| 30 | 1.165 | 1.864 |
| 40 | 1.127 | 1.912 |
| 50 | 1.093 | 1.96 |
| 60 | 1.06 | 2.007 |
| 80 | 1 | 2.099 |
| 100 | 0.946 | 2.188 |
來源: engineeringtoolbox.com
Calculator: Duct Friction Loss
Straight 风管 摩擦 Loss (Darcy-Weisbach)
單位換算器
The source page included a Unit Converter section. This converter preserves the common duct-design conversions for airflow, duct size, pressure loss, length, and velocity.
空氣 风管 單位 转換器
还原的原始源表
The following tables are restored from the original source page to preserve the complete reference data.
工程要點
- Turbulent flow assumption: The Swamee-Jain formula used above is valid for . Almost all HVAC duct systems fall in this range. For , use (laminar flow).
- Rectangular ducts: Convert to equivalent round duct using , or use the equal-friction method tables from ASHRAE/SMACNA.
- Fittings and accessories: The calculator covers straight duct friction only. Add local loss coefficients (-factors) for elbows, tees, transitions, dampers, and grilles. Typical practice applies an equivalent length or loss coefficient method.
- Air density corrections: At elevations above sea level or elevated temperatures, air density drops. Use the density table above or calculate as with .
- Flexible duct penalty: Corrugated flexible ducts have roughness 10–20× that of sheet metal. Manufacturers often recommend adding 50% to the friction loss computed from nominal diameter.
- Standard design velocity: Residential supply mains: 4–6 m/s. Commercial supply: 6–10 m/s. Exhaust: 8–13 m/s. Exceeding these values leads to noise and excessive energy use.
- Equal-friction method: A common design approach sizes all duct sections for a uniform pressure drop per unit length (typically 0.8–1.2 Pa/m for low-pressure systems).
參考资料
- Original Source — Engineering ToolBox
- Original external calculator reference — http://www.iklimnet.com/data/duct.html
- Original source reference: http://www.iklimnet.com/data/duct.html
- ASHRAE Handbook — Fundamentals, Chapter 21: Duct Design
- SMACNA HVAC Duct Construction Standards