WSFU Demand Tables
Water Supply System without Flush Valves
The following table provides estimated demand for water supply systems when the load in WSFU is known, for systems without flush valves.
Water Supply System with Flush Valves
The following table provides estimated demand for water supply systems when the load in WSFU is known, for systems with flush valves.
Important Design Notes
-
Minimum Flow Rate Rule: The minimum flow rate in a system can never be less than the flow demand of the fixture with the highest individual demand.
-
Compensation Factor: The conversion of 1 WSFU = 1 GPM applies only when sizing for a single fixture or a very small number of fixtures. For larger systems, probability curves or demand tables (shown above) must be used to account for the statistical likelihood that not all fixtures operate simultaneously.
-
Special Equipment: When sizing for special equipment or manifolds, use the demand tables above to determine the required flow rate rather than simple unit conversion.