Overview
Engineering reference data for Water Valve KV Diagram in water systems.
Key Formulas
Hydrostatic Pressure
Pressure due to water column.
Flow Rate
Area × velocity.
Variables
| Symbol | Description | Unit |
|---|---|---|
| Pressure | Pa | |
| Flow rate | m³/s | |
| Head/depth | m |
Example Calculations
For a water system where the maximum pressure drop through a modulating control valve is designed to be 100 kPa and the flow is 5 liter/s, the required flow factor () can be determined.
Using the standard Kv relationship for water: Where:
- is the volume flow rate ()
- is the density of water ()
- is the pressure drop ()
This yields an estimated .
Sizing Considerations
A critical practical note from valve engineering: Control valves are intentionally sized smaller than the connecting pipe to ensure stable control.
- For a flow of 5 l/s: The connecting pipe size is typically in the range of 80 - 100 mm (3 - 4 inches) nominal diameter.
- Recommended control valve size: To achieve a of ~20, the valve itself should be selected in the range of 50 - 80 mm (2 - 3 inches) nominal diameter.
Why undersize the valve? Selecting a valve one or two dimensions smaller than the pipe limits the maximum pressure modulating span. This provides a better control range and promotes more stable process control, preventing the valve from operating near its fully open position under normal flow conditions.