Skip to main content
Speclore

Ventilation Dampers

Reference data and engineering information about ventilation dampers for hvac systems applications.

ventilationdampers

Overview

Engineering reference data for Ventilation Dampers in HVAC systems.

Key Formulas

Sensible Heat

Q=m˙cpΔTQ = \dot{m} c_p \Delta T

Heat causing temperature change.

Latent Heat

Q=m˙hfgΔωQ = \dot{m} h_{fg} \Delta\omega

Heat causing moisture change.

COP (Cooling)

COP=Qc/WCOP = Q_c / W

Coefficient of performance.

Variables

Symbol Description Unit
QQ Heat transfer W
m˙\dot{m} Mass flow rate kg/s
cpc_p Specific heat of air J/(kg·K)
ΔT\Delta T Temperature difference K

Damper Classification by Function

Damper Leakage Classification (BS EN 1751:1999)

The leakage class determines the acceptable air leakage through the damper at a 100 Pa pressure difference.

  • *Class 0: No requirements
  • *Class 1: Less than 0.2 m3/s per m20.2 \text{ m}^3\text{/s per m}^2 valve area
  • *Class 2: Less than 0.04 m3/s per m20.04 \text{ m}^3\text{/s per m}^2 valve area
  • *Class 3: Less than 0.008 m3/s per m20.008 \text{ m}^3\text{/s per m}^2 valve area
  • *Class 4: Less than 0.0015 m3/s per m20.0015 \text{ m}^3\text{/s per m}^2 valve area

Air flow rates at 100 Pa are typically available from manufacturer catalogs.

Leakage Flow Rate Calculation

The leakage air flow through a closed damper can be calculated using the pressure difference and manufacturer data at 100 Pa.

ql=q100(Δpl100)1/2q_l = q_{100} \left( \frac{\Delta p_l}{100} \right)^{1/2}

Where:

  • qlq_l = actual volume flow per m² valve area (m³/s per m²)
  • q100q_{100} = volume flow at 100 Pa per m² valve area (m³/s per m²)
  • Δpl\Delta p_l = actual pressure drop through the valve (Pa)

References