Overall Heat Transfer Coefficients

Reference data and engineering information about overall heat transfer coefficients for heat transfer applications.

overallheattransfercoefficientsCalculator

Overview

Engineering reference data for Overall Heat Transfer Coefficients in heat transfer.

Key Formulas

Fourier's Law

q=kTq = -k \nabla T

Heat flux proportional to temperature gradient.

Convective Heat Transfer

Q=hA(TsT)Q = hA(T_s - T_\infty)

Heat transfer between surface and fluid.

Stefan-Boltzmann Law

q=εσT4q = \varepsilon \sigma T^4

Radiative heat flux from a surface.

Thermal Resistance

Rth=LkAR_{th} = \frac{L}{kA}

Resistance to heat conduction.

Variables

Symbol Description Unit
qq Heat flux W/m²
kk Thermal conductivity W/(m·K)
hh Convection coefficient W/(m²·K)
TT Temperature K
ε\varepsilon Emissivity
σ\sigma Stefan-Boltzmann constant 5.67×10⁻⁸ W/(m²·K⁴)

Overall Heat Transfer Coefficient Reference Table

The following table provides rough average values of the overall heat transfer coefficient U for common fluid and material combinations under practically still fluid conditions.

Unit Conversion

The overall heat transfer coefficient can be converted between unit systems using:

1  Btuft2hr°F=5.678  Wm2K=4.882  kcalhrm2°C1 \; \frac{\text{Btu}}{\text{ft}^2 \cdot \text{hr} \cdot °\text{F}} = 5.678 \; \frac{\text{W}}{\text{m}^2 \cdot \text{K}} = 4.882 \; \frac{\text{kcal}}{\text{hr} \cdot \text{m}^2 \cdot °\text{C}}

Practical Example: Water-to-Air Copper Heat Exchanger

Estimate the heat flux for a copper heat exchanger with water at a mean temperature of 80°C on one side and air at 20°C on the other. Using U=13.1  W/(m2⋅K)U = 13.1 \; \text{W/(m}^2\text{·K)}:

q=UΔT=13.1  Wm2K×(80°C20°C)=786  Wm2750800  Wm2q = U \cdot \Delta T = 13.1 \; \frac{\text{W}}{\text{m}^2 \cdot \text{K}} \times (80°C - 20°C) = 786 \; \frac{\text{W}}{\text{m}^2} \approx 750\text{–}800 \; \frac{\text{W}}{\text{m}^2}

Important Considerations

The tabulated values are rough estimates for still or low-velocity fluids. Actual U values depend on:

  • Fluid velocities and flow regime (laminar vs. turbulent)
  • Fluid viscosities and thermal properties
  • Condition of the heating surfaces (fouling, scaling)
  • Temperature difference magnitude
  • Heat exchanger geometry

For precise engineering calculations, always verify with manufacturer data or detailed thermal analysis.

References