Overview
Engineering reference data for Legionella in miscellaneous.
Key Formulas
Unit Conversion
Multiply by conversion factor.
Linear Interpolation
Estimate between two known points.
Percentage
Part as fraction of whole.
Variables
| Symbol | Description | Unit |
|---|---|---|
| Input value | — | |
| Output value | — | |
| Conversion factor | — |
Critical Temperature Ranges
Legionella bacteria exhibit specific thermal behaviors critical for control:
- Growth Range: 69°F (20.5°C) to 122°F (50°C)
- Survival Limit: Cannot survive above 131°F (55°C) for more than 5–6 hours.
- Instantaneous Destruction: Occurs above 158°F (70°C).
For protective design in hot water systems, maintain operating temperatures at or above 140°F (60°C). Note: Water at 140°F can cause full-thickness burns within 10 seconds—always mix down to safe temperatures before delivery at taps. Systems operating below 140°F require enhanced cleaning and chemical treatment protocols.
High-Risk Systems
Particular attention should be directed toward these water systems due to their common operating conditions:
- Cooling towers and evaporative condensers
- Scrubber systems with low temperatures
- Low temperature hot water supply systems
Prevention Strategies
Effective management to inhibit Legionella growth includes:
- Keep basins and sumps free of mud and organic debris.
- Use chemical and organic inhibitors as recommended.
- Prevent water stagnation by ensuring continuous circulation.
- Avoid process leaks into cooling water, as introduced nutrients can promote bacterial growth.