Overview
Engineering reference data for Fan Inlet Pressure in fluid mechanics.
Key Formulas
Reynolds Number
Ratio of inertial to viscous forces — determines flow regime.
Bernoulli's Equation
Conservation of energy for steady, inviscid, incompressible flow.
Continuity Equation
Conservation of mass for incompressible flow.
Darcy-Weisbach
Pressure drop due to friction in a pipe.
Variables
| Symbol | Description | Unit |
|---|---|---|
| Reynolds number | — | |
| Fluid density | kg/m³ | |
| Flow velocity | m/s | |
| Characteristic dimension | m | |
| Dynamic viscosity | Pa·s | |
| Pressure | Pa | |
| Darcy friction factor | — |
Correction Factor Table
When inlet suction pressure exceeds 270 mm W.G (10 in W.G), reduced air density requires compensation using a correction factor:
:::note For suction pressures below 270 mm W.G (10 in W.G), the correction factor is normally neglected and . :::
Corrected Suction Pressure
The corrected suction pressure accounts for reduced air density at high vacuum conditions:
Where:
- = corrected suction pressure (mm W.G. or in W.G.)
- = design (and measured) suction pressure (mm W.G. or in W.G.)
- = pressure correction factor from table above
Example
Given: Design suction pressure mm W.G. (−14 in W.G.)
Solution: From the table, the correction factor
The corrected suction pressure of −395 mm W.G. should be used for proper fan selection.
Unit Conversions
| Unit | Equivalent |
|---|---|
| 1 in water | 248.8 N/m² |
| 1 in water | 0.0361 lb/in² |
| 1 in water | 25.4 kg/m² |
| 1 in water | 0.0739 in mercury |